- Microprocessor technology with watchdog
- An effective analogue low-pass filter for suppressing harmonics when measuring frequency and vector surge
- Digital filtering of the measured values by using discrete Fourier analysis to suppress higher harmonics and DC components induced by faults or system operations
- Integrated functions for voltage, frequency and vector surge in one device.
- Voltage supervision, each with two-step under-/ and overvoltage detection
- Frequency supervision with three-step under or over-frequency (user setting)
- Completely independent time settings for voltage and frequency supervision
- Adjustable voltage threshold value for blocking frequency and vector surge measuring.
- Display of all measuring values and setting parameters for normal operation, as well as tripping via an alphanumeric display and LEDs
- Storage and indication of the tripping values
- In compliance with VDE 0435, part 303 and IEC 255
- For blocking the individual functions by the external blocking input, parameters can be set according to the requirement
- User configurable vector surge measurement, one phase or three phase.
- Reliable vector surge measurement by an exact calculation algorithm

Universal Mains Decoupling Device: MRN2
FEATURES
The MRN2 is a universal mains decoupling device that covers the protection requirements of VDE and most other utilities for the parallel operation of power stations on the mains.
- Over/and undervoltage protection
- Over/ and under-frequency protection
- Extremely fast decoupling of the generator in case of mains failure (MRN2-1) or
- Rate of change of frequency df/dt (MRN2-2)
Because of the combination of three protectional functions in one device, the MRN2 is a very compact mains de-coupling device. Compared to the standardly used single devices, it has a very good price/performance ratio.
The C&S MRN2 Mains De-coupling Relay is a universal protection device primarily used for the mains parallel operation of power stations and generators. Its key benefits and advantages stem from its integrated, microprocessor-based design, which provides comprehensive and rapid protection functions in a single, cost-effective unit.
- Features Over-/Undervoltage Protection with separate time and voltage settings.
- Offers Over-/Underfrequency Protection with completely independent time settings.
- Vector Surge (MRN2-1 model): Provides extremely fast decoupling in case of mains failure
- Rate of Change of Frequency (MRN2-2 model): Detects the instantaneous frequency gradient for added stability and protection against transient processes.