Intelligent Motor Controller (with communication)

FEATURES
  • Over load, Under load, Reverse phase, Phase loss, Locked rotor, Unbalance, E/F protection function
  • Current range 0.125A~60A within one device
  • Different functions selectable within one device, e.g Direct starter, Reversing starter, Y-D starter, Reactor / Inverter starter
  • MCC, Local, Auto, Water level, Remote control
  • Instantaneous under voltage compensation, Auto re-starter function
  • Fault analysis, Fault value storing(Fault recording)
  • Total operating time recording, Setting function Modbus, RS-485 / RS – 422 port

CSMPM - Digital Relays

FEATURES
  • Digital Relay  with built-in MCU (Micro Processor Control Unit).
  • Multiple protection: Over load / Phase failure / Stall /Asymmetry / Phase reverse/ Earth Fault.
  • Current setting 0.5-6A & 5-60A.  Current setting 0.5-6A can be used upto  600A with external Ct’s
  • Fault diagnostic seven segment display of fault & values.
  • Digital Ammeter function.
  • Time setting : Inverse time (0-60 sec), Definite time (0-60 sec) starting & Delay time (0-30 sec) operating time.
  • Accuracy : Current / Time + 5% of setting.
  • Fail safe operation
  • Alert function (60-110% of set current).
  • Inverse / Definite time characteristics, site selectable.
  • C.T. ratio setting in CSMPM-06 frame only.

CSMPA - Analog Relays (CSMPA22/40/80)

Features Inverse Time Characteristics
  • Multiple protection: Over load / Phase failure / Stall /Asymmetry / Phase reverse.
  • Current setting upto 80A in 3 frame sizes.
  • Fault diagnose by LEDs indication.
  • Time setting 0 – 30 sec.
  • Accuracy : Current / Time + 5%.
  • Relays with built-in MCU (Micro Processor Control Unit)
  • Environment operational temperature (-25 C  to +70 C).
  • Compact design & Elegant outlook.
  • Common use of the Screw type & Tunnel type.
  • Applicable to the inverter circuit (20 – 200 Hz).
  • Mounting options : 35mm Din-rail or Screw.
  • Fail safe operation.

CSMPA - Analog Relays (CSMPA 60T)

Features Definite Time Characteristics
  • Protection : Over load & phase failure
  • Time setting : Starting time (0.2-30 sec), Operating time(0.2-15 sec)
  • Accuracy : Current/Time + 5% / (+0.5 sec)
  • Compact Size, Economical
  • Relays with built-in MCU (Micro Processor Control Unit)
  • Current setting: 0.5-6A or 5-60A options. Current setting 0.5-6A can be used upto  600A with external CT’s
  • Looping option is available for FHP Motors
  • Fault diagnostic by LED indication
  • Mounting option: 35mm Din-rail or Screw
  • Prevent Motor Failure
  • Increase Motor Life
  • Reduced Down Time – Improve Productivity
  • Reduce Inventory – Common Model
  • Improve Productivity-Overload Alarm Before Trip
  • Long Life – Maintains Accuracy of Settings
  • Earth Fault Protection – Trip Only The Faulted Motor and not the Incoming Supply